Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1325 Volume (gallons): 39750 Flow measure reading (gpm): 70 Minimum required flow (gpm): 83
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 750 Turnover Rate (min): 567
Total Chlorine (ppm): 5 Free Chlorine (ppm): 5 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 100 Pool water temp ˚F: 79 pH: 7.4 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 16-August-2021

Comments
Equipment available, thorough testing records kept, pool chemicals are good.
Ensure flow rate is greater than 83 gpm.