Sampling Details | |||
---|---|---|---|
Sub Type: Other | Special Feature: | Location: | |
Area: 1160 | Volume (gallons): 35500 | Flow measure reading (gpm): | Minimum required flow (gpm): 74 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 755 | Turnover Rate (min): 480 |
Total Chlorine (ppm): 6 | Free Chlorine (ppm): 6 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 100 | Pool water temp ˚F: 78 | pH: 7.6 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 141 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(6)(k) / Outlet drain covers are secure/meet ANSI/ASME A112.19.8-2007 requirements.
Critical Specifications for the two (2) main drain covers is not available.
Provide the specifications for the drain covers to verify VGB compliance.
3701-31-04 (D)(6)(a) / Pool free chlorine disinfectant residual is above 1 ppm.
Critical Corrected During Inspection The pool free chlorine residual was noted at 0ppm.
Raise and maintain the pool free chlorine reidual at 1ppm minimum.
Liquid chlorine was added at 10:40am by the free chlorine residual was 6.0ppm. Also, the feeder system tubing was replaced during the inspection.
Comments |
---|
No other violations observed during the inspection. Pool Notes: 1. The pool water is clear. 2. ACC unit pH noted at 7.5. 3. Pool turnover rate= 4. Fencing around the pool found in satisfactory condition. 5. Post the 2015 pool license when obtained from CCPH. 6. ACC alarm functions when tested. Inspection conducted by Scott Bradley,R.S. 732-7614 |