Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1160 Volume (gallons): 35500 Flow measure reading (gpm): Minimum required flow (gpm): 74
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 755 Turnover Rate (min): 480
Total Chlorine (ppm): 6 Free Chlorine (ppm): 6 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 100 Pool water temp ˚F: 78 pH: 7.6 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): 141 Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(k) / Outlet drain covers are secure/meet ANSI/ASME A112.19.8-2007 requirements.
Critical Specifications for the two (2) main drain covers is not available.
Provide the specifications for the drain covers to verify VGB compliance.
3701-31-04 (D)(6)(a) / Pool free chlorine disinfectant residual is above 1 ppm.
Critical Corrected During Inspection The pool free chlorine residual was noted at 0ppm.
Raise and maintain the pool free chlorine reidual at 1ppm minimum. Liquid chlorine was added at 10:40am by the free chlorine residual was 6.0ppm. Also, the feeder system tubing was replaced during the inspection.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 02-June-2015

Comments
No other violations observed during the inspection.
Pool Notes:
1. The pool water is clear.
2. ACC unit pH noted at 7.5.
3. Pool turnover rate=
4. Fencing around the pool found in satisfactory condition.
5. Post the 2015 pool license when obtained from CCPH.
6. ACC alarm functions when tested.
Inspection conducted by Scott Bradley,R.S. 732-7614