Sampling Details | |||
---|---|---|---|
Sub Type: Other | Special Feature: | Location: | |
Area: 1160 | Volume (gallons): 35500 | Flow measure reading (gpm): 75 | Minimum required flow (gpm): 74 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 755 | Turnover Rate (min): 480 |
Total Chlorine (ppm): 8 | Free Chlorine (ppm): 8 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 150 | Pool water temp ˚F: 83 | pH: 7.8 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 141 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(6)(k) / Outlet drain covers are secure/meet ANSI/ASME A112.19.8-2007 requirements.
Critical Repeat Specifications for the two (2) main drain covers could not be located.
Provide specifications for the main drain covers to verify VGB compliance.
Comments |
---|
No other violations observed during the inspection. The pool otherwise looks great! Pool Notes: 1. The pool water is clear. 2. ACC unit pH noted at 7.8. 3. Pool turnover rate=7.9 4. Pool records found in satisfactory condition. 5. Post the 2015 pool license when obtained from CCPH. 6. ACC alarm functions when tested. Inspection conducted by Scott Bradley,R.S. 732-7614 |