Sampling Details | |||
---|---|---|---|
Sub Type: Hotel/motel | Special Feature: | Location: | |
Area: 490 | Volume (gallons): 12795 | Flow measure reading (gpm): 60 | Minimum required flow (gpm): 27 |
Disinfectant: Salt | Secondary Disinfectant: | ORP: | Turnover Rate (min): 480 |
Total Chlorine (ppm): 3.5 | Free Chlorine (ppm): 2.5 | Combined Chlorine (ppm): 1 | Total Bromine (ppm): |
Alkalinity (ppm): 50 | Pool water temp ˚F: 83 | pH: 7.3 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 74 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (A) / All construction or alterations of a public swimming pool are approved
Repeat The pool replaced the pump, salt generator, and pH feeder.
Ensure an equipment replacement notification report is submitted for replaced equipment. 3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
Free chlorine, total chlorine, combined chlorine, and pH are not being tested and recorded before the pool is open for use and every 12 hours when the main pool operator is off-site.
Free chlorine, total chlorine, combined chlorine, and pH must be tested and recorded before the pool is open for use and every 12 hours (with ACC use). 3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Corrected During Inspection Total alkalinity was initially measured at 50 ppm.
The operator added sodium bicarbonate to increase total alkalinity.
Comments |
---|
-The disinfectant residuals and water quality parameters meet code requirement. -Alkalinity was measured at 60 ppm, the ideal range is 80-120 ppm. -Combined chlorine was measured at 1 ppm. Hyper-chlorinate (shock) the pool to remove combined chlorine. -All required safety equipment was provided. -The pool perimeter was secure. -The filter pressure was 10 psi. -The pool water was clear. -The ACC unit measured pH at 7.3. -Turnover rate was 213 minutes. If you have any questions or concerns, call Sidney Spurlock at (513) 732-7612. |