Sampling Details | |||
---|---|---|---|
Sub Type: Wading Pool | Special Feature: | Location: | |
Area: 100 | Volume (gallons): 780 | Flow measure reading (gpm): 0 | Minimum required flow (gpm): 6.5 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 815 | Turnover Rate (min): |
Total Chlorine (ppm): 6 | Free Chlorine (ppm): 6 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 100 | Pool water temp ˚F: 68 | pH: 7.6 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
Flow meter not able to provide accurate reading.
Properly install a flow meter or have a pump curve available for every water pump used for the pool.
Comments |
---|
Unable to determine the rate of flow. Ensure that flow meter is assessed or smaller flow meter is put in to be able to get an accurate reading. Water chemistry observed good. Water clarity good. Safety equipment available (spine board, shepherd crook, personal flotation device with 30ft throw line). Emergency telephone functional. |