Sampling Details | |||
---|---|---|---|
Sub Type: Other | Special Feature: | Location: | |
Area: 1800 | Volume (gallons): 54000 | Flow measure reading (gpm): 70 | Minimum required flow (gpm): 113 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: | Turnover Rate (min): |
Total Chlorine (ppm): 8 | Free Chlorine (ppm): 8 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 120 | Pool water temp ˚F: 83 | pH: 7.8 | Cyanuric acid (ppm): 0 |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Weirs missing from skimmer baskets.
All equipment must be maintained in accordance with the manufacturers specifications. Please replace skimmer weirs. 3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met. Flow observed at 70gpm. Minimum flow required is 113 gpm.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
Comments |
---|
Pool water is clear. Disinfectant residuals meet minimum code requirements at this time. Safety equipment provided. Emergency phone functioning during the time of inspection. First Aid kit was supplied and appropriate warning signs were posted. Records look good. Keep up the good work! |