Sampling Details | |||
---|---|---|---|
Sub Type: Other | Special Feature: | Location: | |
Area: 1325 | Volume (gallons): 39750 | Flow measure reading (gpm): 0 | Minimum required flow (gpm): 83 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: | Turnover Rate (min): |
Total Chlorine (ppm): 0 | Free Chlorine (ppm): 0 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 130 | Pool water temp ˚F: 80 | pH: 8.3 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical No chlorine was in pool at time of inspection
Upon opening pool, ensure to add proper amount of disinfection residual and maintain levels in acceptable range.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range upon opening pool.
3701-31-04(D)(6)(a)(2) / Pool free chlorine disinfectant residual shall be above 1 ppm.
Critical Pool free chlorine disinfectant residual was below 1 ppm.
Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above.
Comments |
---|
*Pool was not open at time of inspection* Ensure to balance chemicals in water before opening pool to public (chlorine levels above 1 ppm) ensure to bring down and maintain pH in acceptable range Other than those pool and surrounding areas look great, keep up good work with record keeping any questions please contact 513-560-6177 |