Sampling Details | |||
---|---|---|---|
Sub Type: Wading Pool | Special Feature: | Location: | |
Area: 100 | Volume (gallons): 780 | Flow measure reading (gpm): 40 | Minimum required flow (gpm): 6.5 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 435 | Turnover Rate (min): 120 |
Total Chlorine (ppm): 0.4 | Free Chlorine (ppm): 0.2 | Combined Chlorine (ppm): 0.2 | Total Bromine (ppm): |
Alkalinity (ppm): | Pool water temp ˚F: 84 | pH: 7.4 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 74 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Corrected During Inspection ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low. 3701-31-04 (B)(1)(e) / Automatic Chemical Controller (ACC) shall function properly.
Critical Corrected During Inspection Automatic Chemical Controller (ACC) was not functioning properly at the time of the inspection. ACC is miscalibrated.
Do not operate the pool when the ACC unit is not functioning properly. Ensure that the ACC unit is functioning properly prior to placing the pool back into operation. 3701-31-04 (B)(2) / Authorized representative is on-site or within 30 minutes of pool location
Authorized representative was not on-site or within 30 minutes of pool location.
Make arrangements to have an authorized representative available while pool is in operation. 3701-31-04 (B)(6)(e) / Equipment identification labels are maintained or on file
Repeat Pac Fab Pump does not have legible plate on it.
Replace the missing equipment labels or have the proper equipment information on site for each piece of equipment. 3701-31-04(D)(6)(a)(2) / Pool free chlorine disinfectant residual shall be above 1 ppm.
Critical Corrected During Inspection Pool free chlorine disinfectant residual was below 1 ppm.
Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above.
Comments |
---|
Total alkalinity was greater than 280 ppm. Pool Water was clear. Cyanuric Acid was noted at less than 30 ppm. |