Sampling Details | |||
---|---|---|---|
Sub Type: Apartment/Condo | Special Feature: | Location: | |
Area: 985 | Volume (gallons): 29500 | Flow measure reading (gpm): 40 | Minimum required flow (gpm): 61 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 700 | Turnover Rate (min): 738 |
Total Chlorine (ppm): 3 | Free Chlorine (ppm): 2.5 | Combined Chlorine (ppm): 0.5 | Total Bromine (ppm): |
Alkalinity (ppm): 50 | Pool water temp ˚F: 78 | pH: 7.6 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met. Observed turnover rate of 738 minutes, required turnover is 480 minutes.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve. 3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm. Observed alkalinity at 50 ppm.
Raise the total alkalinity to at least 60 ppm.