Sampling Details
Sub Type: Apartment/Condo Special Feature: Location:
Area: 985 Volume (gallons): 29500 Flow measure reading (gpm): 40 Minimum required flow (gpm): 61
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 700 Turnover Rate (min): 738
Total Chlorine (ppm): 3 Free Chlorine (ppm): 2.5 Combined Chlorine (ppm): 0.5 Total Bromine (ppm):
Alkalinity (ppm): 50 Pool water temp ˚F: 78 pH: 7.6 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met. Observed turnover rate of 738 minutes, required turnover is 480 minutes.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm. Observed alkalinity at 50 ppm.
Raise the total alkalinity to at least 60 ppm.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 18-August-2023