Sampling Details | |||
---|---|---|---|
Sub Type: Other | Special Feature: | Location: | |
Area: 1000 | Volume (gallons): 30000 | Flow measure reading (gpm): 50 | Minimum required flow (gpm): 60 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 792 | Turnover Rate (min): 480 |
Total Chlorine (ppm): 1.75 | Free Chlorine (ppm): 1.75 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 130 | Pool water temp ˚F: 84 | pH: 7.5 | Cyanuric acid (ppm): 20 |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 74 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(4)(a)(iv) / Water temperatures are recorded daily
Water temperatures were not being recorded daily.
Take and record the water temperature at least once/day. 3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met. Measured flow rate of 50 gpm is 10 gpm less than the minimum necessary to achieve completer turnover of pool water volume through the filter every 8 hours.
If possible, throttle the flow to at least 60 gpm but not more than 74 gpm so as not to exceed the maximum filter flow rate. If this is not possible, have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve. 3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Perimeter barrier had gaps greater than 4 inches on the west side of the pool, left of the west entrance gate.
Repair the perimeter barrier so that there are not any gaps greater than 4 inches anywhere along the barrier.
Comments |
---|
Facility inspection notes: Water clarity, disinfectant residuals, and water quality readings meet minimum code requirements at this time. Signage and safety equipment provided as required. Pool looks really good at this time. Keep up the good work. |