Sampling Details | |||
---|---|---|---|
Sub Type: Wading Pool | Special Feature: | Location: | |
Area: 150 | Volume (gallons): 1000 | Flow measure reading (gpm): 30 | Minimum required flow (gpm): 8 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 600 | Turnover Rate (min): 120 |
Total Chlorine (ppm): 0.3 | Free Chlorine (ppm): 0.2 | Combined Chlorine (ppm): 0.1 | Total Bromine (ppm): |
Alkalinity (ppm): 60 | Pool water temp ˚F: 80 | pH: 7.2 | Cyanuric acid (ppm): 0 |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 34 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Repeat Corrected During Inspection ORP reading was below 650 mV. Chlorine residual was also found to be low at the time of the inspection.
Once the chlorine residual was increased, the ORP reading increased correspondingly. Reading at time of report: 653 mV. 3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Corrected During Inspection Chlorine disinfectant residual measured at 0.2 ppm free chlorine was less than 1 ppm for the pool.
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation. Chlorine pump was switched to manual feed during inspection. Residual quickly rose to 3 ppm. Accordingly the pool may remain open. Pump was switched back to ACC control after manual adjustment. 3701-31-04(D)(6)(a)(2) / Pool free chlorine disinfectant residual shall be above 1 ppm.
Critical Corrected During Inspection Pool free chlorine disinfectant residual was below 1 ppm.
Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above.
Comments |
---|
Water clarity, pH and alkalinity meet code requirements. Records maintained. Signage provided. Perimeter barrier -OK. |