Sampling Details
Sub Type: Other Special Feature: Location:
Area: 3200 Volume (gallons): 137500 Flow measure reading (gpm): 425 Minimum required flow (gpm): 287
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: Turnover Rate (min): 480
Total Chlorine (ppm): 5 Free Chlorine (ppm): 5 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 90 Pool water temp ˚F: 78 pH: 7.6 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Corrected During Inspection Equalizer lines were not plugged.
PIC properly plugged the equalizer lines.
3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Repeat The hand rail was not secured.
Repair the hand rail so that it is secure.
3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Repeat Depth markers were not observed on the pool deck.
Add depth markers to the pool deck.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 27-June-2019

Comments
1. Water clarity and disinfectant residuals meet minimum code requirements.
2. Safety equipment provided as required.
3. Pool perimeter was secure
4. Filters psi were 10/11/8/13