Sampling Details
Sub Type: Apartment/Condo Special Feature: Location:
Area: 985 Volume (gallons): 29500 Flow measure reading (gpm): 40 Minimum required flow (gpm): 61
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 715 Turnover Rate (min): 480
Total Chlorine (ppm): 1.5 Free Chlorine (ppm): 1.5 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 60 Pool water temp ˚F: 80 pH: 7.3 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): 98 Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat The main drain cover needed to be replaced in 2014.
Replace the cover to verify VGB compliance.
3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
SVRS/APSOS/ACC test results/ service records were not maintained.
Document periodic testing of the SVRS device in the pool records.
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Weirs are missing from the skimmer baskets.
Replace the missing weirs.
3701-31-04 (B)(6)(k) / Outlet drain covers are secure/meet ANSI/ASME A112.19.8-2007 requirements.
Critical Repeat The main drain cover needed to be replaced in 2014.
Replace the cover to verify VGB compliance.
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical ACC unit alarm testing is not documented.
Document periodic ACC unit testing in the pool records.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 02-August-2018

Comments
Pool Notes:
1. The pool water is clear.
2. ACC unit pH noted at 7.6.
3. ACC alarm functions when tested.
4. All required safety equipment is available.
5. The pool pH was between 7.2-7.4.
6. Pool turnover rate=12.3 hours. It is recommended the pool filter system flow rate be increased to 61 to maintain an eight (8) hour turnover rate.
7. The report was emailed to Mr. Sinkovich.
Contact Scott Bradley,R.S. (732-7614) with any questions.