Sampling Details
Sub Type: Wading Pool Special Feature: Location:
Area: 100 Volume (gallons): 780 Flow measure reading (gpm): 60 Minimum required flow (gpm): 6.5
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 810 Turnover Rate (min): 13
Total Chlorine (ppm): 5 Free Chlorine (ppm): 5 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 70 Pool water temp ˚F: 80 pH: 8.0 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(t) / Equipment/chemical/storage areas are free of hazards/accessible only to authorized personnel.
Critical Equipment/ chemical storage area was accesible to the public
Ensure the chemical and equipment storage area is only accesible to authorized personnel.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8. Observed to be 8.0
Treat the pool water so that the pH is within the acceptable range.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 10-August-2021