Sampling Details
Sub Type: Hotel/motel Special Feature: Location:
Area: 490 Volume (gallons): 12795 Flow measure reading (gpm): 100 Minimum required flow (gpm): 27
Disinfectant: Salt Secondary Disinfectant: ORP: Turnover Rate (min): 480
Total Chlorine (ppm): 0.8 Free Chlorine (ppm): 0.2 Combined Chlorine (ppm): 0.6 Total Bromine (ppm):
Alkalinity (ppm): 80 Pool water temp ˚F: 83 pH: 7.8 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): 74 Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Corrected During Inspection The pool free chlorine residual was noted at 0.2ppm. Increase, then maintain the pool free chlorine residual at 1.0ppm minimum. Ms. Knippenberg agreed to Voluntarily Close the pool.

3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
Repeat SVRS device and ACC unit test results were not documented. Record the periodic testing of these items.
The test results/service records for these devices must be kept on site for review. If the device has not been recently serviced, have the device tested immediately and provide documentation of the test results. Correct By: 16-Jul-2021
3701-31-04 (B)(6)(j) / All SVRS devices are maintained/ functional and tested
Critical SVRS device test results were not documented. Record the periodic testing of this device.
Correct By: 16-Jul-2021
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Repeat ACC unit test results were not documented. Record the periodic testing of the unit.
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly. Correct By: 16-Jul-2021
3701-31-04(D)(6)(a)(2) / Pool free chlorine disinfectant residual shall be above 1 ppm.
Critical Corrected During Inspection The pool free chlorine residual was noted at 0.2ppm. Increase, then maintain the pool free chlorine residual at 1.0ppm minimum. Ms. Knippenberg agreed to Voluntarily Close the pool.
Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 08-July-2021

Comments
Pool Notes:
1. The pool water is clear
2. Turnover rate=2.1 hours.
3. Filter pressure gauge reads 10psi.
4. ACC unit pH reads 7.4, Free chlorine reads 1.0ppm.
5. SVRS and ACC unit alarms functioned when tested.
6. The report was emailed to the facility.