Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1840 Volume (gallons): 62400 Flow measure reading (gpm): Minimum required flow (gpm): 130
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 730 Turnover Rate (min):
Total Chlorine (ppm): 6 Free Chlorine (ppm): 6 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 130 Pool water temp ˚F: 83 pH: 7.9 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
Repeat A means of determining rate-of-flow was not readable. Flow meter stuck or the size of the meter is not the proper size to get an accurate reading.
Properly install a flow meter or have a pump curve available for every water pump used for the pool.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 22-June-2022

Comments
Notes:
1. Ensure first aid kit is properly supplied with gloves.
2. Emergency telephone available.
3. Proper signage observed.
4. Flow measure reading could not be obtained due to flow meter stuck. Ensure flow meter is replaced with one that is an appropriate size, or fixed so that a proper reading can be done to ensure circulation requirements are being met.
5. Follow up inspection required to determine if flow rate is meeting turnover requirements.