Sampling Details
Sub Type: Spray Ground Special Feature: Location:
Area: 17 Volume (gallons): 600 Flow measure reading (gpm): 75 Minimum required flow (gpm): 20
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 785 Turnover Rate (min):
Total Chlorine (ppm): 1 Free Chlorine (ppm): 1 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 40 Pool water temp ˚F: 80 pH: 7.4 Cyanuric acid (ppm): 0
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Repeat Corrected During Inspection Chlorine disinfectant residual was less than 2 ppm for the sprayground
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 2 ppm or above prior to placing the sprayground back into operation.
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
3701-31-04(D)(6)(a)(6) / Spray ground free chlorine disinfectant residual shall be above 2 ppm.
Critical Repeat Corrected During Inspection Spray ground free chlorine disinfectant residual was below 2 ppm.
Do not operate the sprayground until the chlorine disinfectant is at 2 ppm or above.


Inspection Information


[?] Facility Type: Special Use Pool

[?] Inspection Type: Standard

[?] Inspection Date: 10-July-2019

Comments
Spray pad was clear and free of debris.
Safety equipment was available.
Safety signs were posted.
Operator Jeff arrived promptly to resolve issues at the time of inspection.
Keep up the good work.