Sampling Details
Sub Type: Apartment/Condo Special Feature: Location:
Area: 750 Volume (gallons): 22500 Flow measure reading (gpm): 60 Minimum required flow (gpm): 47
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: Turnover Rate (min): 480
Total Chlorine (ppm): 6 Free Chlorine (ppm): 6 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 140 Pool water temp ˚F: 81 pH: 8.2 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): 120 Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Repeat Weirs are missing from the skimmers. Replace the missing weirs.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat The pool pH was noted at 8.2 (2 drops of acid demand lowered the pH to 7.6). Lower the pH to between 7.2-7.8.
Treat the pool water so that the pH is within the acceptable range.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 29-August-2023

Comments
No other violations observed during the inspection.
The pool otherwise looks great!
Pool Notes:
1. Pressure gauge noted at 12psi.
2. Turnover rate=6.25 hours.
3. The pool water is clear.
4. All required safety equipment is available.
5. The report was emailed to the facility.
Contact Scott Bradley,R.E.H.S. (732-7614) with any questions.