Sampling Details | |||
---|---|---|---|
Sub Type: Wading Pool | Special Feature: | Location: | |
Area: 136 | Volume (gallons): 1530 | Flow measure reading (gpm): 55 | Minimum required flow (gpm): 13 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 707 | Turnover Rate (min): 120 |
Total Chlorine (ppm): 1 | Free Chlorine (ppm): 1 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 60 | Pool water temp ˚F: 83 | pH: 7.5 | Cyanuric acid (ppm): 0 |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 38 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(4)(a)(vi) / Total alkalinity is tested weekly
Repeat Total alkalinity was not tested weekly. In fact, onsite records indicate that total alkalinity has yet to be tested in 2016.
Test total alkalinity and record the result in the daily pool operation reports at least once each week. 3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
pH probe is reading a pH of 6.7 when the actual measured value in the pool is 7.5.
Clean and recalibrate the pH probe so that it gives an accurate measurement of the pH of the pool water. All equipment must be maintained in accordance with the manufacturers specifications. 3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. Observed flow rate of 55 gpm exceeds the maximum flow capacity of 38 gpm listed on the sand filter.
Throttle down the flow rate (if possible) to between 17-38 gpm so as to comply with 2 hour turnover rate requirement without ecxeeding the maximum filter flow rate capacity of the sand filter. All equipment must be maintained in accordance with the manufacturers specifications.
Comments |
---|
Facility inspection notes: Water clarity disinfectant residuals and water quality readings meet minimum code requirements at this time. Onsite records indicate that the ACC pressure and pump shut off switches were tested the week of 7/24-7/30. Another 30-day test is due this week. Pool looks good at this time. Thanks for your time and efforts this 2016 pool season. Drain covers are not due for replacement until 2018. Reminder: pool records must be retained for 2 years. |