Sampling Details | |||
---|---|---|---|
Sub Type: Apartment/Condo | Special Feature: | Location: | |
Area: 985 | Volume (gallons): 29500 | Flow measure reading (gpm): 100 | Minimum required flow (gpm): 61 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 635 | Turnover Rate (min): 480 |
Total Chlorine (ppm): 1.5 | Free Chlorine (ppm): 1 | Combined Chlorine (ppm): 0.5 | Total Bromine (ppm): |
Alkalinity (ppm): 80 | Pool water temp ˚F: 76 | pH: 7.5 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv. Ensure unit is calibrated so that it is maintained properly.
Have the ACC unit inspected to determined why the ORP is low. 3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. Ensure that all skimmer weirs are available/fastened correctly
All equipment must be maintained in accordance with the manufacturers specifications.
Comments |
---|
Pool Notes: 1. The pool water is clear. 2. ACC unit pH noted at 7.6. 3. ACC alarm functions when tested. 4. All required safety equipment is available. 5. The pool main drain was replaced in 2018. |