Sampling Details
Sub Type: Camp Special Feature: Location:
Area: 1350 Volume (gallons): 25000 Flow measure reading (gpm): 45 Minimum required flow (gpm): 62
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: Turnover Rate (min): 480
Total Chlorine (ppm): 4 Free Chlorine (ppm): 4 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 110 Pool water temp ˚F: 80 pH: 7.4 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): 62 Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 19-June-2019