Sampling Details | |||
---|---|---|---|
Sub Type: Camp | Special Feature: | Location: | |
Area: 1350 | Volume (gallons): 25000 | Flow measure reading (gpm): 45 | Minimum required flow (gpm): 62 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: | Turnover Rate (min): 480 |
Total Chlorine (ppm): 4 | Free Chlorine (ppm): 4 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 110 | Pool water temp ˚F: 80 | pH: 7.4 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 62 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.