Sampling Details | |||
---|---|---|---|
Sub Type: Wading Pool | Special Feature: | Location: | |
Area: 150 | Volume (gallons): 1000 | Flow measure reading (gpm): | Minimum required flow (gpm): 8 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 606 | Turnover Rate (min): 120 |
Total Chlorine (ppm): 4 | Free Chlorine (ppm): 4 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 60 | Pool water temp ˚F: 83 | pH: 7.2 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 40 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 ( D )(6)(a) / ORP reading is above 650 mv
The ACC unit ORP was noted at 606mv.
Increase the ORP to 650mv minimum. Correct By: 23-Jul-2014 3701-31-04 (B)(1)(a) / Outlet covers are installed/secured/in compliance
Critical Specifications have not been provided for the two (2) main drain covers.
Provide specifications (Manufacturer, Model#, Install and Replacement dates) for the main drain covers. 3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
The fitter pressure gauge is not working.
Please repair. Correct By: 23-Jul-2014 3701-31-04 (D)(7)(c) / Audible/visual alarm when unit is malfunctioning or when pH or ORP levels are not acceptable.
The ACC unit alarm could not be tested.
Determine a way to test the ACC unit alarm. Correct By: 23-Jul-2014
Comments |
---|
Pool Notes: 1. Turnover rate=0.4 hours. 2. ACC unit pH noted at 6.9. 3. The pool water is clear. Inspection conducted by Scott Bradley,R.S. 732-7614 |