Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1160 Volume (gallons): 35500 Flow measure reading (gpm): 50 Minimum required flow (gpm):
Disinfectant: Secondary Disinfectant: ORP: 780 Turnover Rate (min): 710
Total Chlorine (ppm): 5 Free Chlorine (ppm): 5 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 60 Pool water temp ˚F: 80 pH: 6.9 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8. Observed to be 6.9
Treat the pool water so that the pH is within the acceptable range.
3701-31-04 (E)(3)(a) / "WARNING, NO LIFEGUARD", sign posted
Corrected During Inspection The unguarded pool was in use without the "WARNING, NO LIFEGUARD" sign posted.
Post the WARNING, NO LIFEGUARD sign in a conspicuos location at all times the pool is available for use.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 11-August-2021

Comments
Chlorine and alkalinity meet requirements. pH was low at 6.9. There was no WARNING-NO LIFEGUARD ON DUTY sign. Sign was put up during inspection. A better method of hanging the sign is recommended.