Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1650 Volume (gallons): 51000 Flow measure reading (gpm): 120 Minimum required flow (gpm): 110
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 647 Turnover Rate (min): 480
Total Chlorine (ppm): 8 Free Chlorine (ppm): 8 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 90 Pool water temp ˚F: 82 pH: 7.5 Cyanuric acid (ppm): 10
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): 141 Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Repeat ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B)(4)(a)(ii) / Combined chlorine is tested daily at pool side prior to use
DPD Reagent #3 was not being used from the test kit provided. Therefore, total chlorine is not being tested as the records state.
Ensure total chlorine is tested using DPD Reagent #3, every 12 hours the pool is in use.
3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
ACC test results were not maintained.
Test the ACC no flow shut-off switch monthly and record the results. The ACC no flow shut-off switch is properly functioning.
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
One skimmer weir was missing.
Replace the missing skimmer weir.
3701-31-04 (B)(6)(y) / Chemicals are properly stored/used
Critical Corrected During Inspection A tub of white powdered chemical is stored unlabeled in the equipment room.
Label and properly store all chemical containers to avoid a chemical reaction or unnecessary exposure.
3701-31-04 (E)(2)(d) / First aid kit provided
Repeat Gloves were not provided in the first aid kit.
Ensure gloves are provided in the first aid kit at all times.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 03-August-2015

Comments
-The disinfectant residuals and water quality parameters meet code requirement.
-Free chlorine was 8 ppm, ideal range is 2-4 ppm.
-All required safety equipment was provided (see violation for gloves).
-The pool perimeter was secure.
-The filter pressure was 16 psi.
-The pool water is clear.
-The ACC unit measured pH at 7.7.
-Turn over rate was 424 minutes.
If you have any questions or concerns, call me at (513) 732-7612.