Sampling Details | |||
---|---|---|---|
Sub Type: Other | Special Feature: | Location: | |
Area: 1650 | Volume (gallons): 51000 | Flow measure reading (gpm): 120 | Minimum required flow (gpm): 110 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 647 | Turnover Rate (min): 480 |
Total Chlorine (ppm): 8 | Free Chlorine (ppm): 8 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 90 | Pool water temp ˚F: 82 | pH: 7.5 | Cyanuric acid (ppm): 10 |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 141 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Repeat ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low. 3701-31-04 (B)(4)(a)(ii) / Combined chlorine is tested daily at pool side prior to use
DPD Reagent #3 was not being used from the test kit provided. Therefore, total chlorine is not being tested as the records state.
Ensure total chlorine is tested using DPD Reagent #3, every 12 hours the pool is in use. 3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
ACC test results were not maintained.
Test the ACC no flow shut-off switch monthly and record the results. The ACC no flow shut-off switch is properly functioning. 3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
One skimmer weir was missing.
Replace the missing skimmer weir. 3701-31-04 (B)(6)(y) / Chemicals are properly stored/used
Critical Corrected During Inspection A tub of white powdered chemical is stored unlabeled in the equipment room.
Label and properly store all chemical containers to avoid a chemical reaction or unnecessary exposure. 3701-31-04 (E)(2)(d) / First aid kit provided
Repeat Gloves were not provided in the first aid kit.
Ensure gloves are provided in the first aid kit at all times.
Comments |
---|
-The disinfectant residuals and water quality parameters meet code requirement. -Free chlorine was 8 ppm, ideal range is 2-4 ppm. -All required safety equipment was provided (see violation for gloves). -The pool perimeter was secure. -The filter pressure was 16 psi. -The pool water is clear. -The ACC unit measured pH at 7.7. -Turn over rate was 424 minutes. If you have any questions or concerns, call me at (513) 732-7612. |