Sampling Details | |||
---|---|---|---|
Sub Type: Apartment/Condo | Special Feature: | Location: | |
Area: 1615 | Volume (gallons): 63447 | Flow measure reading (gpm): | Minimum required flow (gpm): |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: | Turnover Rate (min): 480 |
Total Chlorine (ppm): 3 | Free Chlorine (ppm): 3 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 120 | Pool water temp ˚F: 81 | pH: 7.3 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
No critical violations were documented at the time of inspection.
No violations were documented at the time of inspection.
The following violation(s) have been corrected since the last inspection. |
---|
3701-31-04 (B)(1)(d)/Circulation/Disinfection system shall operate properly. Disinfection system was not operating properly at the time of the inspection. The disinfectent system was not operating. Do not operate the pool when disinfection system is not operating properly. Ensure that the disinfection system is functioning properly prior to placing the pool back into operation. |
3701-31-04 (B)(4)(a)(i)/Disinfection residuals are tested daily at pool side at required intervals for pools/automatic chemical controllers/special features Disinfection residuals were not tested daily at pool side and at the required intervals for pools. Total chlorine was not being tested. Test the disinfection residual every day before bathers enter the water. Disinfection residual must then be tested every 4 hours when an ACC is not in use. Make sure to test for free and total chlorine. |
3701-31-04 (B)(4)(a)(ii)/Combined chlorine is tested daily at pool side prior to use Combined chlorine was not tested daily at pool side prior to use. Test for combined chlorine prior to bathers entering the water and every 4 hours the pool is open for use. |
3701-31-04 (B)(4)(a)(vi)/Total alkalinity is tested weekly Total alkalinity was not tested weekly. Test total alkalinity at least once/week. |
3701-31-04 (B)(6)/Equipment is maintained per manufacturers specifications. Equipment was not maintained per manufacturers specifications, skimmer weirs were missing. All equipment must be maintained in accordance with the manufacturers specifications, Make sure to replace each of the missing skimmer weirs. |
3701-31-04 (B)(6)(i)/A means of determining rate-of-flow on all water pumps A means of determining rate-of-flow was not found for all water pumps, one of the flow meters was broken. Properly replace the broken flow meter or have a pump curve available for every water pump used for the pool. |
3701-31-04 (D)(02)/Public swimming pool is continuously disinfected using a chemical feeding device connected to the circulation system The pool was not being continuously disinfected using a chemical feeding device connected to the circulation system Repair or replace the disinfection system so that the pool is continuously being disinfected. |
Comments |
---|
The disinfectant feeder was hooked up and properly working. Disinfectant residuals were met. All issues were corrected. Thanks. |