Sampling Details | |||
---|---|---|---|
Sub Type: Camp | Special Feature: | Location: | |
Area: 1350 | Volume (gallons): 25000 | Flow measure reading (gpm): | Minimum required flow (gpm): |
Disinfectant: | Secondary Disinfectant: | ORP: | Turnover Rate (min): |
Total Chlorine (ppm): 10 | Free Chlorine (ppm): | Combined Chlorine (ppm): | Total Bromine (ppm): |
Alkalinity (ppm): | Pool water temp ˚F: | pH: 7.6 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Flow rate exceeds filter maximum flow rate.
All equipment must be maintained in accordance with the manufacturers specifications. 3701-31-04 (B)(6)(c)(i) / Backflow prevention devices shall be maintained.
Repeat Observed no backflow prevention device on fill hose.
Have the backflow prevention device evaluated or replaced so that backflow is prevented. Provide backflow prevention device (ASSE 1011).
The following violation(s) have been corrected since the last inspection. |
---|
3701-31-04 (B)(6)(s)/Perimeter barrier is in good repair to prevent unauthorized entry Door into pool enclosure does not self latch. Ensure door self closes and self latches. Until door can be repaired such that it self closes and self latches, operator has agreed to either monitor door while pool is open or close pool and lock entrance. Door will be fixed later in day according to operator. |
Comments |
---|
Inspection notes: - Door self closed and self latched. Thank you! |