Sampling Details
Sub Type: Hotel/motel Special Feature: Location:
Area: 418 Volume (gallons): 12500 Flow measure reading (gpm): 45 Minimum required flow (gpm): 26
Disinfectant: Salt Secondary Disinfectant: ORP: 760 Turnover Rate (min): 278
Total Chlorine (ppm): 2 Free Chlorine (ppm): 1.5 Combined Chlorine (ppm): 0.5 Total Bromine (ppm):
Alkalinity (ppm): 60 Pool water temp ˚F: 82 pH: 7.5 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(4)(a)(iv) / Water temperatures are recorded daily
Water temperatures were not being recorded daily.
Take and record the water temperature at least once/day.
3701-31-04 (E)(2)(d) / First aid kit provided
Repeat First aid equipment was not provided.
Provide first aid equipment, including a first aid kit, at the pool at all times.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 11-May-2023

Comments
Ensure 30ft rope is attached to personal flotation device. PIC connected rope to device.
Water temperature to be recorded daily in log; ensure to check water clarity daily.
Water chemistry within recommended parameters.