Sampling Details | |||
---|---|---|---|
Sub Type: Other | Special Feature: | Location: | |
Area: 1800 | Volume (gallons): 54000 | Flow measure reading (gpm): | Minimum required flow (gpm): 113 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 644 | Turnover Rate (min): |
Total Chlorine (ppm): 2 | Free Chlorine (ppm): 1.5 | Combined Chlorine (ppm): 0.5 | Total Bromine (ppm): |
Alkalinity (ppm): 160 | Pool water temp ˚F: 80 | pH: 7.6 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Repeat ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low. 3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Turnover rate could not be determined. Ensure that the flow meter is replaced.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve. 3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Repeat Required meters and gauges were not maintained or were not functional while the pool is in operation. The flow meter is not easily readable.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation. 3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Repeat Ladders/stairs/steps were loose.
Repair or replace the ladders/stairs/steps so that they are slip resistant and in good repair. 3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Depth markers were faded. Ensure that the depth markers are repainted.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated.
Comments |
---|
Inspection Notes: 1. Pool water observed clear. 2. pH noted at 7.6 3. Ensure old gloves are replaced in both first aid kits. 4. Ensure that the flow meter is replaced with one that is easily readable. |