Sampling Details
Sub Type: Hotel/motel Special Feature: Location:
Area: 490 Volume (gallons): 12795 Flow measure reading (gpm): 80 Minimum required flow (gpm): 27
Disinfectant: Calcium Hypochlorite Secondary Disinfectant: ORP: Turnover Rate (min): 480
Total Chlorine (ppm): 4 Free Chlorine (ppm): 4 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 120 Pool water temp ˚F: 85 pH: 8.2 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): 74 Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
The filter pressure gauge does not appear to be working. Repair the gauge.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat The pool pH was noted at 8.2 (Three drops of acid demand lowered the pH to 7.4). Lower, then maintain the pool pH between 7.2-7.8.
Treat the pool water so that the pH is within the acceptable range.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 14-April-2023

Comments
Pool Notes:
1. All necessary safety equipment is available.
2. New disinfectant system information was obtained..
3. The pool water was clear.
4. Turnover rate=2.7 hours.
5. ACC unit pH reads 7.5.
6. The report was emailed to the facility.
Contact Scott Bradley,R.E.H.S. (732-7614) with any questions.