Sampling Details | |||
---|---|---|---|
Sub Type: Hotel/motel | Special Feature: | Location: | |
Area: 490 | Volume (gallons): 12795 | Flow measure reading (gpm): 80 | Minimum required flow (gpm): 27 |
Disinfectant: Calcium Hypochlorite | Secondary Disinfectant: | ORP: | Turnover Rate (min): 480 |
Total Chlorine (ppm): 4 | Free Chlorine (ppm): 4 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 120 | Pool water temp ˚F: 85 | pH: 8.2 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 74 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
The filter pressure gauge does not appear to be working. Repair the gauge.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation. 3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat The pool pH was noted at 8.2 (Three drops of acid demand lowered the pH to 7.4). Lower, then maintain the pool pH between 7.2-7.8.
Treat the pool water so that the pH is within the acceptable range.
Comments |
---|
Pool Notes: 1. All necessary safety equipment is available. 2. New disinfectant system information was obtained.. 3. The pool water was clear. 4. Turnover rate=2.7 hours. 5. ACC unit pH reads 7.5. 6. The report was emailed to the facility. Contact Scott Bradley,R.E.H.S. (732-7614) with any questions. |