Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1160 Volume (gallons): 35500 Flow measure reading (gpm): 90 Minimum required flow (gpm): 74
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 740 Turnover Rate (min): 480
Total Chlorine (ppm): 1.5 Free Chlorine (ppm): 1.5 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 120 Pool water temp ˚F: 83 pH: 7.6 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): 141 Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (A)(1) / Public swimming pool is licensed
Repeat The 2018 Swimming Pool License could not be located.
Post the 2018 Swimming Pool License.
3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat Specifications could not be located for the two (2) main drain covers.
Provide specifications for the covers to verify VGB compliance.
3701-31-04 (B)(6)(k) / Outlet drain covers are secure/meet ANSI/ASME A112.19.8-2007 requirements.
Critical Repeat Specifications could not be located for the two (2) main drain covers.
Provide specifications for the drain covers to verify VGB compliance.
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
The entrance gate does not latch when closed.
Repair the entrance gate so it latches when closed. Correct By: 29-Jun-2018
3701-31-04 (E)(2)(a)(ii) / A USCG Type IV personal flotation device with 30 -60 foot throw line provided
Repeat A 30 -60 foot throw line was not provided with the life ring.
Provide a 30 -60 foot throw line with the life ring. Correct By: 29-Jun-2018


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 21-June-2018

Comments
Pool Notes:
1. The pool water is clear.
2. ACC unit pH noted at 7.6
3. Pool turnover rate=6.6 hours.
4. Filter pressure gauge noted at 10psi.
5. Record periodic ACC unit testing in the pool records.
6. The report was emailed to Ms. Butts.
Contact Scott Bradley,R.S. (732-7614) with any questions