Sampling Details
Sub Type: Apartment/Condo Special Feature: Location:
Area: 750 Volume (gallons): 22500 Flow measure reading (gpm): 70 Minimum required flow (gpm): 47
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: Turnover Rate (min): 480
Total Chlorine (ppm): 8 Free Chlorine (ppm): 8 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 130 Pool water temp ˚F: 80 pH: 7.4 Cyanuric acid (ppm): 0
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): 113 Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
The pressure gauge on the filter is not functioning properly.
Repair the pressure gauge to ensure it functions properly.
3701-31-04 (E)(2)(d) / First aid kit provided
Repeat Gloves were not provided in the first aid kit.
Provide gloves in the first aid kit.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 14-June-2016

Comments
-The disinfectant residuals and water quality parameters meet code requirement.
-Free chlorine was measured at 8 ppm, the ideal range is 2-4 ppm.
-All required safety equipment was provided.
-The pool perimeter was secure.
-The filter pressure was unable to be determined.
-The pool water is clear.
-Turn over rate was 321 minutes.