Sampling Details | |||
---|---|---|---|
Sub Type: Apartment/Condo | Special Feature: | Location: | |
Area: 750 | Volume (gallons): 22500 | Flow measure reading (gpm): 70 | Minimum required flow (gpm): 47 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: | Turnover Rate (min): 480 |
Total Chlorine (ppm): 8 | Free Chlorine (ppm): 8 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 130 | Pool water temp ˚F: 80 | pH: 7.4 | Cyanuric acid (ppm): 0 |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 113 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
The pressure gauge on the filter is not functioning properly.
Repair the pressure gauge to ensure it functions properly.
3701-31-04 (E)(2)(d) / First aid kit provided
Repeat Gloves were not provided in the first aid kit.
Provide gloves in the first aid kit.
Comments |
---|
-The disinfectant residuals and water quality parameters meet code requirement. -Free chlorine was measured at 8 ppm, the ideal range is 2-4 ppm. -All required safety equipment was provided. -The pool perimeter was secure. -The filter pressure was unable to be determined. -The pool water is clear. -Turn over rate was 321 minutes. If you have any questions or concerns, call me at (513) 732-7612. |