Sampling Details | |||
---|---|---|---|
Sub Type: Camp | Special Feature: | Location: | |
Area: 1350 | Volume (gallons): 25000 | Flow measure reading (gpm): 30 | Minimum required flow (gpm): 62 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: | Turnover Rate (min): 480 |
Total Chlorine (ppm): 6 | Free Chlorine (ppm): 6 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 100 | Pool water temp ˚F: 88 | pH: 7.4 | Cyanuric acid (ppm): 0 |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 62 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (A) / All construction or alterations of a public swimming pool are approved
Pool Chlorinator was changed.
Submit Equipment change notification form to ODH. 3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
The licensee /authorized representative was not keeping or maintaining operational records for this week.
All facility records must be maintained and available for review upon request. 3701-31-04 (B)(4)(a)(ii) / Combined chlorine is tested daily at pool side prior to use
Repeat Combined chlorine was not tested daily at pool side prior to use.
If ACC is in use combined chlorine must be tested every 12 hours while the pool is in use. 3701-31-04 (B)(4)(a)(vi) / Total alkalinity is tested weekly
Total alkalinity was not tested weekly.
Test total alkalinity at least once/week. 3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
Repeat ACC test results records were not maintained.
The test results/service records for these devices must be kept on site for review. If the device has not been recently serviced, have the device tested immediately and provide documentation of the test results. 3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve. 3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat Door to pool does not latch and has no latch.
Operator has agreed to close pool until it can be ensured that door latches in addition to self closing.
Comments |
---|
- Operator has made changes to decking and fencing and put in a new door in addition to changes noted in equipment inventory. Operator will be notified in regards to if plans need to be submitted to Ohio Department of Health. - Shepherds crook, first aid kit, Personal flotation device and throw line, spine board, emergency phone were provided. - Do not operate pool until it can be ensured that door self closes and self latches. Pool operator closed pool at time of inspection and locked door. - Pool water was clear. - Ensure numbers are posted with sign indicating location of nearest emergency phone as specified in 3701-31-04. |