Sampling Details | |||
---|---|---|---|
Sub Type: Other | Special Feature: | Location: | |
Area: 1696 | Volume (gallons): 52000 | Flow measure reading (gpm): 110 | Minimum required flow (gpm): 109 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 830 | Turnover Rate (min): 480 |
Total Chlorine (ppm): 1 | Free Chlorine (ppm): 1 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 70 | Pool water temp ˚F: 85 | pH: 6.8 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 74 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat The two (2) main drain covers needed to be replaced in 2012.
Replace the drain covers to verify VGB Compliance.
3701-31-04 (B)(6)(k) / Outlet drain covers are secure/meet ANSI/ASME A112.19.8-2007 requirements.
Critical Repeat The two (2) main drain covers needed to be replaced in 2012.
Replace the drain covers to verify VGB compliance.
3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
The bottom step of a five (5) foot end ladder is damaged.
Repair or replace the damaged step. Correct By: 30-Aug-2018
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
The pool pH was noted at 6.8. Fourteen (14) drops of Base Demand increased the pH to 7.2.
Increase and maintain the pool pH between 7.2-7.8. Correct By: 30-Aug-2018
Comments |
---|
No other violations observed during the inspection. The pool otherwise Looks Great! Pool Notes: 1. ACC unit alarm testing is documented in pool records. The alarm functions when tested. 2. The pool water is clear. 3. Proper safety equipment is available for use. 4. ACC unit pH noted at 7.2. 5. Pool turnover rate=7.9 hours. 6. Filter pressure gauges noted at 10psi. 7. The 2018 Swimming Pool License is posted. 8. The report was emailed to Ms. Butts. Contact Scott Bradley,R.S. (732-7614) with any questions. |