Sampling Details
Sub Type: Wading Pool Special Feature: Location:
Area: 110 Volume (gallons): 1350 Flow measure reading (gpm): Minimum required flow (gpm):
Disinfectant: Secondary Disinfectant: ORP: Turnover Rate (min):
Total Chlorine (ppm): Free Chlorine (ppm): Combined Chlorine (ppm): Total Bromine (ppm):
Alkalinity (ppm): Pool water temp ˚F: pH: Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Repeat Depth markers/deck warning signs were not maintained in a clearly legible/visible manner.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated. At least 2 depth markers must be reinstalled at the wading pool. NOTE: "No Diving" signs are NOT required at wading pools.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Follow-up

[?] Inspection Date: 11-August-2017

The following violation(s) have been corrected since the last inspection.
3701-31-04 (B)(1)(b)/SVRS device(s) shall be functional.
The SVRS device that is being used as a secondary means to prevent entrapment/evisceration was not functional at the time of the inspection.
Do not operate the pool when the SVRS is not functioning. Repair or replace the Vac Alert SVRS Device so that a secondary means of preventing entrapment is provided as required. Ensure the SVRS is operating properly prior to placing the pool back into operation.
3701-31-04 (B)(6)(j)/All SVRS devices are maintained/ functional and tested
SVRS device was not tested in accordance with the manufacturer's specifications.
Have the SVRS device tested immediately and maintain the test results on site. Vac Alert SVRS Device was tested during inspection and failed to cavitate the pump as designed.
3701-31-04 (B)(6)(j)/All SVRS devices are maintained/ functional and tested
SVRS devices were not maintained or not functional.
Restore all SVRS devices to proper working order to prevent entrapment or evisceration.
Comments
At time of inspection, the new Vac Alert functioned properly.
Thank you for making those corrections.