Sampling Details | |||
---|---|---|---|
Sub Type: Apartment/Condo | Special Feature: | Location: | |
Area: 1615 | Volume (gallons): 63447 | Flow measure reading (gpm): 140 | Minimum required flow (gpm): 132 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: | Turnover Rate (min): 480 |
Total Chlorine (ppm): 2 | Free Chlorine (ppm): 2 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 100 | Pool water temp ˚F: 75 | pH: 7.6 | Cyanuric acid (ppm): 20 |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 98 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(4)(a)(vi) / Total alkalinity is tested weekly
Repeat Total alkalinity was not tested weekly.
Test total alkalinity at least once/week. 3701-31-04 (B)(4)(a)(vii) / Cyanuric acid is tested weekly
Repeat Cyanuric acid was not tested weekly.
Test for cyanuric acid level at least once/week.
Comments |
---|
-The disinfectant residuals and water quality parameters meet code requirement. -All required safety equipment was provided. -The pool perimeter was secure. -The filter pressure was 11/12 psi. -The pool water was clear. -The Stingl switch was functioning correctly. -Turn over rate was 453 minutes. If you have any questions or concerns, call Mackinzie Dickman at (513) 732-7602. |