Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1696 Volume (gallons): 52000 Flow measure reading (gpm): 90 Minimum required flow (gpm): 109
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 710 Turnover Rate (min):
Total Chlorine (ppm): 2 Free Chlorine (ppm): 2 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 90 Pool water temp ˚F: 80 pH: 7.6 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met. Observed flow rate of 80 at time of inspection. Ensure turnover rate of 480 minutes is met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 21-August-2023

Comments
Pool water clear
All safety equipment is available
Ensure the minimum required flow of at least 109 gpm is met to be in compliance with the required 480 minute turnover rate.