Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1325 Volume (gallons): 39750 Flow measure reading (gpm): 100 Minimum required flow (gpm): 83
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 800 Turnover Rate (min): 397
Total Chlorine (ppm): 9 Free Chlorine (ppm): 9 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 120 Pool water temp ˚F: 84 pH: 7.9 Cyanuric acid (ppm): 0
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): 141 Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(4)(a)(iv) / Water temperatures are recorded daily
Water temperatures were not being recorded daily.
Take and record the water temperature at least once/day.
3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
ACC test results/ service records were not maintained.
The test results/service records for these devices must be kept on site for review. If the device has not been recently serviced, have the device tested immediately and provide documentation of the test results.
3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Ladder rail on the shallow side of the pool and the ladder on the left side of the pool (towards pump room) was not secured properly to the pool deck surface.
Repair or replace the ladders/stairs/steps so that they are slip resistant and in good repair.
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat The black gate in the rear end of pool will close with force but it is not self latching.
Repair the gate, so that it is both self closing and self latching.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
The pH was noted at 7.9. Ideal range is 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
3701-31-04 (E)(2)(b)(i) / 12 ft. non-telescopic reach pole with Sheppard's crook & a USCG Type IV personal flotation device with 30 - 60 foot throw line.
The reach pole provided was telescopic.
Provide 12 ft. non-telescopic reach pole with Shepherd's crook.
3701-31-04 (E)(2)(d) / First aid kit provided
First aid equipment was not provided.
Provide first aid equipment, including a first aid kit, at the pool at all times.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 20-July-2016

Comments
1. Pool water is clear.
2. The pressure on the filter was noted at 15psi.
3. Turnover rate was noted at 6.6 hrs.