Sampling Details | |||
---|---|---|---|
Sub Type: Wading Pool | Special Feature: | Location: | |
Area: 150 | Volume (gallons): 1000 | Flow measure reading (gpm): 40 | Minimum required flow (gpm): 8 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 565 | Turnover Rate (min): |
Total Chlorine (ppm): 1 | Free Chlorine (ppm): 1 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 60 | Pool water temp ˚F: 84 | pH: 7.8 | Cyanuric acid (ppm): 0 |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Repeat ORP reading was below 650 mv. ORP observed at 565mv.
Have the ACC unit inspected to determined why the ORP is low.
Comments |
---|
Pool water was clear. Disinfectant residuals meet minimum code requirements at this time. Safety equipment and warning signs were available. Only 1 pair of disposable gloves provided in first aid kit. Daily clarity observations and weekly alkalinity and cyanuric acid readings are not being recorded consistently. Pool looks good. Keep up the good work. |