Sampling Details | |||
---|---|---|---|
Sub Type: Other | Special Feature: | Location: | |
Area: 1000 | Volume (gallons): 30000 | Flow measure reading (gpm): 70 | Minimum required flow (gpm): 63 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 617 | Turnover Rate (min): 480 |
Total Chlorine (ppm): 3 | Free Chlorine (ppm): 3 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 110 | Pool water temp ˚F: 81 | pH: 7.5 | Cyanuric acid (ppm): 0 |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 98 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Repeat ORP reading was below 650 mV. Chlorine residual was 3.0 at the time.
Have the ACC unit inspected to determined why the ORP is low.
Comments |
---|
No other violations noted at this time. Water clarity, disinfectant residuals, and water quality readings meet minimum code requirements at this time. Signage and safety equipment provided as required. Restrooms are clean and properly supplied. Pool looks really good at this time. Keep up the good work! |