Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1000 Volume (gallons): 30000 Flow measure reading (gpm): 70 Minimum required flow (gpm): 63
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 617 Turnover Rate (min): 480
Total Chlorine (ppm): 3 Free Chlorine (ppm): 3 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 110 Pool water temp ˚F: 81 pH: 7.5 Cyanuric acid (ppm): 0
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): 98 Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Repeat ORP reading was below 650 mV. Chlorine residual was 3.0 at the time.
Have the ACC unit inspected to determined why the ORP is low.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 14-August-2018

Comments
No other violations noted at this time.
Water clarity, disinfectant residuals, and water quality readings meet minimum code requirements at this time.
Signage and safety equipment provided as required.
Restrooms are clean and properly supplied.
Pool looks really good at this time. Keep up the good work!