Sampling Details | |||
---|---|---|---|
Sub Type: Apartment/Condo | Special Feature: | Location: | |
Area: 1615 | Volume (gallons): 63447 | Flow measure reading (gpm): 140 | Minimum required flow (gpm): 132 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: | Turnover Rate (min): 480 |
Total Chlorine (ppm): 6 | Free Chlorine (ppm): 6 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 100 | Pool water temp ˚F: 80 | pH: 7.5 | Cyanuric acid (ppm): 0 |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 98 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(6)(j) / All SVRS devices are maintained/ functional and tested
Critical Corrected During Inspection SVRS device was not tested in accordance with the manufacturer's specifications.
Have the SVRS device tested immediately and maintain the test results on site. Device was tested during inspection by this inspector and found to be functioning properly. Test result was documented in facility's weekly pool operation and incident report. Make certain that the SVRS device is tested at least once every 30 days and the results of the test are recorded in the weekly pool operation and incident reports.
Comments |
---|
Facility inspection notes: Water clarity, disinfectant residuals, water quality readings meet minimum code requirements. Signage and safety equipment provided as required. Pool looks great! Please keep up the good work! |