Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1325 Volume (gallons): 39750 Flow measure reading (gpm): 90 Minimum required flow (gpm): 83
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 680 Turnover Rate (min): 480
Total Chlorine (ppm): 6 Free Chlorine (ppm): 6 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 110 Pool water temp ˚F: 82 pH: 7.3 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): 141 Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Weirs are missing in the skimmer baskets.
Replace the missing weirs.
3701-31-04 (B)(6)(k) / Outlet drain covers are secure/meet ANSI/ASME A112.19.8-2007 requirements.
Critical Repeat Specifications could not be located for the two (2) main drain covers.
Provide specifications for the drain covers (Install/Replace dates) to verify VGB compliance.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Follow-up

[?] Inspection Date: 21-August-2015

The following violation(s) have been corrected since the last inspection.
3701-31-04 (B)(6)(s)/Perimeter barrier is in good repair to prevent unauthorized entry
The entrance gate will close with force, but will not latch.
Repair the entrance gate so it is self closing, and will latch. Cincinnati Pool Management was contacted regarding the issue.Correct By: 21-Aug-2015
3701-31-04 (E)(2)(e)/Working emergency telephone/call box provided.
There is no emergency telephone at the pool.
Provide a working emergency telephone. Cincinnati Pool Management was contacted regarding the issue. Correct By: 21-Aug-2015
Comments
All violations scheduled to be corrected, were corrected.
Pool Notes:
1. The pool water is clear.
2. ACC unit pH noted at 7.4.
3. Pool turnover rate=7.4 hours.
4. Post the 2015 pool license when obtained from CCPH.
5. The pool pH was between 7.2-7.4.
6. Copy of the inspection report was left with pool records.
Reinspection conducted by Scott Bradley,R.S. 732-7614