Sampling Details
Sub Type: Wading Pool Special Feature: Location:
Area: 150 Volume (gallons): 1000 Flow measure reading (gpm): 40 Minimum required flow (gpm): 8
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 610 Turnover Rate (min): 25
Total Chlorine (ppm): 1 Free Chlorine (ppm): 1 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 90 Pool water temp ˚F: 81 pH: 7.6 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 23-June-2020

Comments
Have ACC tested to determine why ORP reading is low
Otherwise pool looks great, water is clear and surrounding areas are well maintained
Record keeping is great
Keep up the good work!

Any questions contact Michael at 513-560-6177