Sampling Details | |||
---|---|---|---|
Sub Type: Wading Pool | Special Feature: | Location: | |
Area: 110 | Volume (gallons): 1350 | Flow measure reading (gpm): | Minimum required flow (gpm): |
Disinfectant: | Secondary Disinfectant: | ORP: | Turnover Rate (min): |
Total Chlorine (ppm): 10 | Free Chlorine (ppm): 10 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 130 | Pool water temp ˚F: 85 | pH: 7.0 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
A means of determining rate-of-flow was not found for all water pumps. .Flow meter is stuck
Properly install a flow meter or have a pump curve available for every water pump used for the pool. 3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Perimeter barrier had gaps greater than 4 inches. Bent Rungs produce gaps greater than 4 inches in places. Gates do not self close and self latch.
Repair the perimeter barrier so that there are not any gaps greater than 4 inches anywhere along the barrier. Perimeter gates are locked at night and there is always a lifegaurd on deck according to operator.
Comments |
---|
Inspection notes: - Lifeguard certification was provided. - Pool water was clear. - SVRS system tested weekly. |