Sampling Details | |||
---|---|---|---|
Sub Type: Wading Pool | Special Feature: | Location: | |
Area: 100 | Volume (gallons): 780 | Flow measure reading (gpm): | Minimum required flow (gpm): 6.5 |
Disinfectant: | Secondary Disinfectant: | ORP: | Turnover Rate (min): 120 |
Total Chlorine (ppm): 1.5 | Free Chlorine (ppm): 1.5 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 90 | Pool water temp ˚F: 82 | pH: 7.6 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 74 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(4)(a)(iv) / Water temperatures are recorded daily
Water temperatures were not being recorded daily.
Take and record the water temperature at least once/day. 3701-31-04 (B)(4)(a)(vi) / Total alkalinity is tested weekly
Total alkalinity was not tested weekly.
Test total alkalinity at least once/week. 3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
Repeat ACC test results/ service records were not maintained.
The test results/service records for these devices must be kept on site for review. If the device has not been recently serviced, have the device tested immediately and provide documentation of the test results. 3701-31-04 (B)(6)(e) / Equipment identification labels are maintained or on file
Pump of wading pool model could not be located on pump.
Replace the missing equipment labels or have the proper equipment information on site for each piece of equipment. 3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
Repeat A means of determining rate-of-flow was not found for all water pumps. Since flow rate was lower than minimum on flow meter, flow rate and pool turn over rate could not be determined.
Properly install a flow meter or have a pump curve available for every water pump used for the pool.
Comments |
---|
Inspection notes: - Flow rate was noted at 40 gpm. - Pool water was clear. - Cyanuric Acid was noted at less than 30 ppm. - First aid kit, phone, shepherd's crook, spineboard, and throw ring were provided. - Appropriate signs were posted. |