Sampling Details | |||
---|---|---|---|
Sub Type: Wading Pool | Special Feature: | Location: | |
Area: 100 | Volume (gallons): 1100 | Flow measure reading (gpm): 40 | Minimum required flow (gpm): 9 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: | Turnover Rate (min): 480 |
Total Chlorine (ppm): 10 | Free Chlorine (ppm): 10 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 100 | Pool water temp ˚F: 78 | pH: 7.2 | Cyanuric acid (ppm): 0 |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 63 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
SVRS test results/ service records were not maintained.
The test results/service records for these devices must be kept on site for review. If the device has not been recently serviced, have the device tested immediately and provide documentation of the test results. 3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
A no diving sign was not posted.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated. 3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was measured at 8.4.
Acid was added to the pool and pH was measured at 7.2.
Comments |
---|
-The disinfectant residuals and water quality parameters meet code requirement. -Free chlorine was 10 ppm, ideal range is 1-2 ppm. -All required safety equipment was provided. -The pool perimeter was secure. -The filter pressure was 8 psi. -The pool water is clear. -Turn over rate was 0.45 hours. If you have any questions or concerns, call me at (513) 732-7612. |