Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1160 Volume (gallons): 35500 Flow measure reading (gpm): 110 Minimum required flow (gpm): 74
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 795 Turnover Rate (min): 480
Total Chlorine (ppm): 4 Free Chlorine (ppm): 4 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 90 Pool water temp ˚F: 82 pH: 7.2 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Observed missing skimmer weir. Ensure all skimmer weirs are in place and functional.
All equipment must be maintained in accordance with the manufacturers specifications.
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Repeat Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly. Records did not reflect that the unit is being tested monthly.
Provide records indicating that the unit is being tested monthly.
3701-31-04 (E)(2)(e) / Working emergency telephone/call box provided.
Repeat Could not locate working emergency phone.
Ensure that an emergency phone is provided.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 07-July-2021

Comments
Inspection Notes:
1. Water is visibly clear.
2. pH noted at 7.2
3. Pool is at proper disinfection levels.
4. Ensure an emergency phone is provided.
5. Ensure that ACC unit is tested and recorded monthly.

Pool looks great!