Sampling Details
Sub Type: Apartment/Condo Special Feature: Location:
Area: 1615 Volume (gallons): 63447 Flow measure reading (gpm): Minimum required flow (gpm):
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: Turnover Rate (min): 480
Total Chlorine (ppm): 1 Free Chlorine (ppm): 1 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 80 Pool water temp ˚F: pH: 7.5 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

No critical violations were documented at the time of inspection.

No violations were documented at the time of inspection.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Follow-up

[?] Inspection Date: 14-July-2021

The following violation(s) have been corrected since the last inspection.
3701-31-04 (B)(1)(d)/Circulation/Disinfection system shall operate properly.
The pool free chlorine residual was noted at 0.6ppm. Raise, then maintain the pool free chlorine level at 1.0ppm minimum.
Correct By: 09-Jul-2021
3701-31-04 (B)(4)(c)/SVRS/APSOS/ACC test results/ service records are maintained
SVRS device and the ACC unit test results were not in pool records. Test, then record monthly testing of these items.
The test results/service records for these devices must be kept on site for review. If the device has not been recently serviced, have the device tested immediately and provide documentation of the test results. Correct By: 09-Jul-2021
3701-31-04 (B)(6)(j)/All SVRS devices are maintained/ functional and tested
SVRS device and the ACC unit test results were not in pool records. Test, then record monthly testing of these items.
Correct By: 09-Jul-2021
3701-31-04 (B)(6)(r)/Safety line(s) are maintained
A safety line was not provided in the pool. Provide a safety line to make swimmers aware of the depth changes.
Safety lines must be in place when required to alert the bathers of the change in depth of the pool. Correct By: 09-Jul-2021
3701-31-04 (D)(7)(d)/Flow or pressure switch with a shut off valve shall be provided and tested monthly.
ACC unit test results were not in pool records. Test, then record monthly testing of the device.
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly. Correct By: 09-Jul-2021
3701-31-04(D)(6)(a)(2)/Pool free chlorine disinfectant residual shall be above 1 ppm.
The pool free chlorine residual was noted at 0.6ppm. Raise, then maintain the pool free chlorine level at 1.0ppm minimum.
Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above.
Comments
All violations were corrected.
Thanks!
Pool Notes:
1. The follow-up inspection scheduled for 7/9/2021 was rescheduled.
2. ACC and SVRS device alarms functioned when tested. Test results are documented in records.
3. The pool pH was between 7.4-7.6.
4. Copy of the report was emailed to Ms. Michelson.