Sampling Details | |||
---|---|---|---|
Sub Type: Other | Special Feature: | Location: | |
Area: 1325 | Volume (gallons): 39750 | Flow measure reading (gpm): 55 | Minimum required flow (gpm): 83 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: | Turnover Rate (min): 480 |
Total Chlorine (ppm): 3 | Free Chlorine (ppm): 3 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 100 | Pool water temp ˚F: 81 | pH: 7.7 | Cyanuric acid (ppm): 30 |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 141 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
Repeat The licensee /authorized representative was not keeping or maintaining operational records.
Pool hours are at 13 hours Sunday through Thursday and 15 hours on Friday and Saturday and record indicate that there is only one test being done a day.
All facility records must be maintained and available for review upon request.
3701-31-04 (B)(4)(a)(ii) / Combined chlorine is tested daily at pool side prior to use
Repeat Combined chlorine was not tested every 12 hours the pool was in use.
Test for combined chlorine prior to bathers entering the water and if ACC is in use combined chlorine must be tested every 12 hours while the pool is in use.
3701-31-04 (B)(4)(a)(iii) / pH is tested daily at pool side at required intervals for pools/automatic chemical controllers/special features
Repeat pH was not tested daily at required intervals for pools/automatic chemical controllers/special features.
pH must be tested prior to bathers entering the water and if ACC is in use pH must be tested every 12 hours while the pool is in use.
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met. Turnover rate was at 723 min.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve. Turnover rate should be at 480 min.
Comments |
---|
-The disinfectant residuals and water quality parameters meet code requirement. -All required safety equipment was provided. -The pool perimeter was secure. -The filter pressure was 22 psi. -The pool water was clear. -Turn over rate was 723 minutes - Pool is operating 13 hours a day Sunday-Thursday and 15 hours a day Friday and Saturday. Combined Chlorine and pH need to be tested every 12 hours or the pool hours can be shortened, If you have any questions or concerns, call Mackinzie Dickman at (513) 732-7602. |