Sampling Details | |||
---|---|---|---|
Sub Type: Wading Pool | Special Feature: | Location: | |
Area: 136 | Volume (gallons): 1530 | Flow measure reading (gpm): 10 | Minimum required flow (gpm): 3 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 265 | Turnover Rate (min): 153 |
Total Chlorine (ppm): 0 | Free Chlorine (ppm): 0 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 100 | Pool water temp ˚F: 79 | pH: 8.0 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low. 3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Chlorine disinfectant residual was less than 1 ppm for the pool
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation. 3701-31-04 (B)(4)(a)(vi) / Total alkalinity is tested weekly
Total alkalinity was not tested weekly.
Test total alkalinity at least once/week. 3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range. 3701-31-04(D)(6)(a)(2) / Pool free chlorine disinfectant residual shall be above 1 ppm.
Critical Pool free chlorine disinfectant residual was below 1 ppm.
Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above.
Comments |
---|
Notes: -Safety equipment available. -Pool clear. -Operator was called regarding chlorine levels. One or more of the critical violations noted on this report may pose an imminent health hazard. Operator voluntarily closed the pool until chlorine levels were fixed. |