Sampling Details
Sub Type: Hotel/motel Special Feature: Location:
Area: 490 Volume (gallons): 12795 Flow measure reading (gpm): 45 Minimum required flow (gpm): 27
Disinfectant: Salt Secondary Disinfectant: ORP: 725 Turnover Rate (min): 384
Total Chlorine (ppm): 4.5 Free Chlorine (ppm): 3.5 Combined Chlorine (ppm): 1 Total Bromine (ppm): 0
Alkalinity (ppm): 70 Pool water temp ˚F: 78 pH: 7.6 Cyanuric acid (ppm): 0
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
Repeat Corrected During Inspection ACC test results/ service records were not maintained. ACC tests not recorded. Ensure to test ACC monthly and record. ACC tested during inspection and found to be properly working.
The test results/service records for these devices must be kept on site for review. If the device has not been recently serviced, have the device tested immediately and provide documentation of the test results.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 28-June-2019

Comments
The disinfectant residuals and water quality parameters meet code requirement. The recommended range is 2-4 ppm. Make sure the free chlorine stays above 1.0 ppm.

-All required safety equipment was provided.
-The pool perimeter was secure.
-The filter pressure was 10 psi.
- The facility uses salt and acid to create chlorine. Therefore the pool is disinfected using chlorine.
Ensure ACC is tested and recorded monthly. Thanks.
- Pool records properly recorded.
- ORP at 725mv, pH on ACC at 7.32.

Keep up the good work.

If you have any questions or concerns, call Bela Perler at 513-732-7612.